Comments on: Boiler Starting Failure – Troubleshooting https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/?utm_source=rss&utm_medium=rss&utm_campaign=boiler-starting-failure-troubleshooting The Maritime Industry Guide Thu, 03 Nov 2022 14:14:44 +0000 hourly 1 https://wordpress.org/?v=6.5.2 By: Abdul Syakur https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4791228 Thu, 03 Nov 2022 14:14:44 +0000 https://www.marineinsight.com/?p=1402#comment-4791228 Why composite boiler cannot auto operation but emergency operation possible

]]>
By: Alan Corlett https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4790956 Thu, 20 Oct 2022 06:06:09 +0000 https://www.marineinsight.com/?p=1402#comment-4790956 Has nobody checked for excessive water in the fuel

]]>
By: Vikas P https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4787518 Thu, 12 May 2022 04:03:44 +0000 https://www.marineinsight.com/?p=1402#comment-4787518 Issue of flame trouble and extraneous light alarm how can i solve the problem

]]>
By: josephus relente https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4761242 Sat, 27 Mar 2021 22:32:04 +0000 https://www.marineinsight.com/?p=1402#comment-4761242 What is the root cause of flame eye or photoelectric cell damage?

]]>
By: mc bogi https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4755764 Thu, 14 Jan 2021 13:31:12 +0000 https://www.marineinsight.com/?p=1402#comment-4755764 auto firing is ok, but when fire manually,fan is only running but no purging at all..our boiler is aalborg..tnx

]]>
By: Pushpendra https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4736295 Fri, 17 Jul 2020 02:30:10 +0000 https://www.marineinsight.com/?p=1402#comment-4736295 Sir facing flue gas temp.high alarm .cleaned tubes with air.boiler is saacke and burner is SKVJM 14, Before flame was bright orange but now flame is more like red than orange.
Used many soot sticks but still giving alarm after every 3or 4hours.belt tightness also checked.Apms is okey.pls advise….regards

]]>
By: Prosper https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4735920 Thu, 25 Jun 2020 18:53:11 +0000 https://www.marineinsight.com/?p=1402#comment-4735920 Very useful

]]>
By: Engr. uzomah https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4735772 Tue, 16 Jun 2020 11:22:35 +0000 https://www.marineinsight.com/?p=1402#comment-4735772 what could cause an Aalborg mission 2000 boiler to explode when the emergency shutdown button is activated

]]>
By: M. Bogdan https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4734724 Fri, 13 Mar 2020 18:44:20 +0000 https://www.marineinsight.com/?p=1402#comment-4734724 Hello, i have an Auxiliary Boiler RP-400M-I burner from Kangrim and i have the follow problem :

I am ruining on MDO and yesterday during day time we received alarm ”Flame Failure”, we opened the burner checked electrodes(were OK) and clean all the filters, after restart boiler fired for around 14 hours. After 14 hours we received same alarm, again cleaned filters but this time with out success. Next day we opened the boiler and re-adjust the electrodes, cleaned filters again but with out any success. We changed also the nozzle with new one, with out any succes also.
After all of above we start it in manual mode(emergency mode) and started, but it takes around 5-8 seconds to keep pressed ignition button(for the spark of electrodes) and the valve for oil open, for the boiler to start firing. The pressure is in range, around 28 BAR in ring line.We also drained the MDO tank to check if it has water, but no water in MDO is present.
For auto operation, my boiler burner controller is from SIEMENS LAL 2.25 and its set for 2.5 seconds to give spark to my electrodes, this set point is from factory and i cant open the box to increase/decrease this set point, because for manual operation(emergency start) i have different burner controller.

The boiler run on auto operation for like 14 days with out any problem in MDO.

What can be the problem? Do you have any advice? Can it be the MDO? or this Burner controller from SIEMENS is not working properly?

]]>
By: Anish https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4707629 Tue, 09 Jul 2019 07:35:51 +0000 https://www.marineinsight.com/?p=1402#comment-4707629 In reply to Munir.

@Munir: Do check the timer and the pilot burner assembly.

]]>
By: Munir https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4705942 Tue, 02 Jul 2019 15:19:00 +0000 https://www.marineinsight.com/?p=1402#comment-4705942 In my vessel use boiler saacke burner , pilot burner can firing , but main burner / automizer can’t following firing , but leave a alarm trip flame eye fail , we use mdo , can you give me advice ?

]]>
By: Dine bautista https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-4703384 Wed, 19 Jun 2019 18:15:14 +0000 https://www.marineinsight.com/?p=1402#comment-4703384 Hello sir, when boiler is ignite in purging position what is the problem?our boiler is saacke.. i can start only in emergency mode. I’ll wait for your reply

]]>
By: Juan John https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-3683755 Sun, 24 Mar 2019 12:28:18 +0000 https://www.marineinsight.com/?p=1402#comment-3683755 Have a different problem here on our Saacke Boiler,
Switch on Automatic mode after low steam pressure, no response from the boiler.
Then switch to Manual, combustion air fan is running but cannot increase or decrease load/damper, tried to fire the Igniter and Oil valve did not activate,. the rotary cup atomizer did not run also.
What could be the problem?

]]>
By: shaheen alam https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-3682271 Mon, 18 Mar 2019 13:31:12 +0000 https://www.marineinsight.com/?p=1402#comment-3682271 sir my ship boiler igniter is on but ignition pump not running. boiler trip by sequence failure. what is tge reason for ignition pump not running? thanks.

]]>
By: Anish https://www.marineinsight.com/tech/boiler/boiler-starting-failure-troubleshooting/#comment-3674794 Tue, 29 Jan 2019 07:09:10 +0000 https://www.marineinsight.com/?p=1402#comment-3674794 In reply to Danne yaril.

@Danne: Do check the nozzle of the pilot burner for the angle and length of the spray ( as per the manual). Also, flame eye needs to be cleaned.

]]>